NFPA Tank Placement General Guidelines
The following
general guidelines are provided as a starting
reference point when building or planning a
residential construction or remodel project. We
strongly encourage you to contact Weaver Gas for
guidance and safety advice specific to your
particular project.
A printable PDF version of these guidelines is
available here.
Location of DOT Containers

Location of ASME Containers

Notes:
1.
Regardless of its size, any ASME tank filled on-site
must be located so that the filling connection and
fixed level gauge are at least 10 feet from external
sources of ignition (i.e. open flame, window A/C,
compressor, etc), intake to direct vented gas
appliance or intake to a mechanical ventilation
system.
2. May be
reduced to a 10 feet minimum for a single container
of 1200 gallons water capacity or less if it is
located at least 25 feet from any other LP-Gas
container of more than 125 gallons water capacity.
3. Minimum
distances from underground containers shall be
measured from the relief valve and filling or level
gauge vent connection at the container, except that
no part of the underground container shall be less
than 10 feet from a building of line of adjoining
property which may be built upon.
4. Where the
container may be subject to abrasive action or
physical damage due to vehicular traffic or other
causes it must be either, (a) placed not less than 2
feet below grade; (b) otherwise protected against
such physical damage.
All Federal, State and
Local ordinances and regulations must be observed at
all times.